StatGardenREF. DESK
Calculators/Everyday/Generator sizing
Everyday

Generator sizing calculator

Generator capacity needed to cover a set of appliances, including starting surge.

Published 6 August 2026 · Updated 24 September 2026

What this calculator does

Generator sizing is driven by the worst moment, not the average one. Motors draw several times their running current for a second or two at startup, so a load that runs at 3,000 W but surges to 4,500 W has to be sized against the 4,500.

Two adjustments then apply on top. Power factor converts real watts into the apparent power the alternator actually has to supply, and a target operating capacity keeps the generator off its own limit, since running continuously at full rating shortens its life and leaves nothing for anything unexpected. At 0.8 power factor and 70% capacity, a 4,500 W surge calls for a generator of about 8,036 W.

The formula

FormulaApparent power = surge watts / power factor; generator size = apparent power / target operating capacity

The surge figure is divided by the power factor to give apparent power in volt-amps, which is what the alternator has to produce. That is then divided by the target operating capacity so the generator runs at the intended fraction of its rating rather than flat out. The headroom line checks the result against the running load, and the coverage line confirms the sizing actually holds it.

TermMeaning
Running wattsSteady draw once everything is up and running.
Surge wattsThe brief peak at startup, driven by the largest motor starting, commonly two to three times its running draw.
Power factorThe ratio of real power to apparent power. 1.0 for heaters and incandescent lighting, around 0.8 for motors and mixed loads.
Operating capacityThe fraction of its rating you intend the generator to run at. 0.7 is a common target, leaving 30% in reserve.

The inputs explained

FieldWhat to enter
Total running watts (W)Total steady watts of everything running at once. This is checked against the result rather than used to size it, see the FAQ.
Peak surge watts (largest startup load included) (W)The highest instantaneous demand, which is the running total plus the extra startup draw of the single largest motor. Motors do not usually all start at the same moment.
Power factorPower factor as a decimal. Use 1.0 for purely resistive loads, and around 0.8 where motors or electronics are involved.
Target operating capacityThe share of the generator rating you want to be using. 0.7 is a reasonable target for sustained running.

When to use it

Sizing a backup generator for a house

The large motors, usually a fridge, freezer, air conditioner or pump, set the surge figure. Sizing against the biggest one starting while everything else runs gives a realistic peak rather than an unnecessarily pessimistic one.

Powering tools on a site

Compressors and saws have heavy startup draws relative to their running load, which is why a generator that handles them comfortably once running can stall when one is switched on.

Checking whether an existing generator is adequate

Running your actual loads through and comparing the recommendation against what you own shows whether it is genuinely sized for the job or merely getting away with it.

Worked examples

Every figure in the tables below is produced by this page’s own calculator at build time, so the numbers and the tool always agree. Select any row to load that scenario.

How does the startup surge drive the generator size?

The same 3,000 W running load with an increasing startup surge.

3,000 W running, 0.8 power factor, 70% target capacity
Surge wattsRecommended generator sizeIn kVAApparent power required
3,500 W6,250 W6.25 kVA4,375 VA
4,000 W7,143 W7.14 kVA5,000 VA
4,500 W8,036 W8.04 kVA5,625 VA
5,500 W9,821 W9.82 kVA6,875 VA
7,000 W12,500 W12.50 kVA8,750 VA
The running load is identical in every row and the recommendation still more than doubles, from 6,250 W to 12,500 W, purely on the startup surge. The two divisions are what open the gap: dividing by 0.8 and then by 0.7 together multiply the surge figure by about 1.79 before anything else is considered.

At what running load does the sizing stop being enough?

The surge held fixed while the steady running load rises, to show where the coverage check fails.

A 4,500 W surge, with the running load increasing
Running wattsRecommended generator sizeHeadroom over running wattsCovers the running load?
3,000 W8,036 W2,625 WYes
4,000 W8,036 W1,625 WYes
5,000 W8,036 W625 WYes
5,625 W8,036 W0 WYes
6,000 W8,036 W-375 WNo, size up further
The recommended size never changes, because it is calculated from the surge alone. What changes is whether it is sufficient: headroom falls to exactly zero at 5,625 W and the answer flips to no at 6,000 W. Above that point the surge is no longer the binding constraint and the sizing has to be driven by the running load instead.

Questions

Why does changing the running watts not change the recommendation?

Because the sizing is calculated from the surge figure, which is normally the larger constraint. The running load is used for the coverage check instead. If that check comes back as no, the surge is no longer what limits you and the generator needs sizing against the running load directly.

How do I work out my surge figure?

Take the total running watts and add the extra startup draw of the single largest motor, not of all of them. Motors rarely start simultaneously. A motor typically surges to two or three times its running draw, and the figure is sometimes given on the appliance plate as locked rotor amps.

What power factor should I use?

1.0 for purely resistive loads such as heaters, kettles and incandescent lamps, where watts and volt-amps are the same. Around 0.8 for anything with motors, transformers or switch-mode supplies, which is most mixed household or site loads. Generator ratings in kVA assume a power factor, usually 0.8.

Why not run the generator at its full rating?

Because the rating is normally a peak rather than a figure for sustained use, and running at it continuously runs hot, increases wear and leaves no margin for anything you did not plan for. Around 70% is a common target. Running very lightly loaded is not ideal either, particularly on diesel units, where it causes wet stacking.

For converting between watts, amp-hours and watt-hours, see the watt-hours calculator. For what running an appliance costs to power, see the electricity bill calculator.